Best Practices:
When Stainless Isn’t So Stainless

Friday, December 20, 2013

More items for Good Technical Practice

Comment | More

“Stainless“ steel is the name given to a group of corrosion-resistant and high-temperature steels that possess in excess of 10.5 - 11% chromium content.

Their remarkable resistance to corrosion comes from the chromium-rich oxide film that forms on the surface. In the presence of moisture, ordinary carbon steel forms iron oxide (rust). Rust is not protective and, eventually, the entire piece of steel will corrode and be converted to rust.

But when enough chromium (more than about 10%) is added to ordinary steel, the oxide produced on the surface is a very thin, virtually invisible layer that provides protection from a wide range of corrosive media.

Gateway-Arch
Wikimedia Commons / Daniel Schwen

In the early 1960s, designers thought the stainless-steel exterior of the Gateway Arch in St. Louis would be impervious to corrosion and surface staining, even without coating. Time, unfortunately, showed otherwise. The National Park Service is now working on a remedy.

This is “stainless” steel, and there are different types and grades that vary widely in corrosion resistance, strength, and performance properties. Common types include austenitic, ferritic, martensitic, and duplex.

Why Paint Stainless Steel?

Stainless steel is often used without a coating except for aesthetic purposes (if, for example, the architect wants to change the color).

However, it is important to note that all stainless steels are not created equal: There are various grades of stainless, and cheaper grades will corrode when exposed to marine environments, chemicals, or high humidity. Such grades may require a rust-inhibitive primer or system for protection, just as mild steel would.

That’s what the inspector found when called to investigate a problem at an upscale, handsome, new pool complex.

The Case of the Rusty Duct

The concrete ceiling above the expansive indoor pool was coated with a white epoxy and carried a large stainless-steel air duct more than five feet in diameter.

Rusting Pool Duct
MPI

All stainless steel is not created equal. Unprotected, cheaper grades will corrode when exposed to marine environments, chemicals, or high humidity.

Six months after the facility opened, telltale spots of red and white corrosion started forming on the duct’s joints and connections—and started to spread. When bits of rust started falling into the pool, the exasperated facility owner took action.

His frustration was compounded by the fact that the stainless-steel hand railings around and inside the pool were in flawless condition, even though their exposure environment (immersion, splash and spill) was more aggressive than that of the rusting duct above.

Stainless v. Stainless

The inspector’s investigation determined that the duct was made of low-grade stainless steel brought in from overseas—proving once again the age-old adage that you get what you pay for. The hand railings, which came from a different source, were indeed high-grade stainless steel appropriate for marine exposure.

Installing a new duct was out of the question, so the only solution was to paint the rusting duct with an anti-corrosive paint system.

However, the use of conventional methods for surface preparation and paint application were also out of the question: The new pool with its fine tile walls and floors and adjacent exercise area were on the ground floor of an occupied high-rise condominium, and the owner demanded that the work be done without generating excessive noise, dust or debris, let alone overspray.

Surface Prep

Stainless-steel surface preparation requires two steps: removing any surface contaminants (such as dirt, oil, grease, and other foreign matter), then roughening the surface.

Gateway Arch-North Leg
National Park Service

The stainless-steel exterior of the legs of the Gateway Arch—the tallest monument in the U.S.—were never coated and have been showing corrosion.

Because stainless is a smooth substrate, it can be difficult to obtain adequate adhesion for the coating system, so the preferred method for roughening the surface is a sweep blast (SSPC-SP 7 Brush-Off Blast Cleaning).

Since neither blasting nor any type of power tool could be used on this project, the inspector recommended application of a highly concentrated solution of MPI #25 Cleaner, Etcher for Galvanized Metal to clean and dull the surface.

Because spraying was not an option, the solution was sponged and wiped on to avoid dripping on any adjacent surfaces. After carefully rinsing the surface, the ducts were then hand-sanded with 150-grit silicon carbide abrasive paper, in an effort to assure some kind of tooth on the surface.

A test patch was then coated with the new paint system: an epoxy primer (MPI #101) topcoated with a two-part aliphatic polyurethane (MPI #72). Much to the inspector's and owner’s relief, the adhesion of the test patch proved sufficient, so the rest of the duct was brushed and rolled with the system.

One year later, the duct is still in pristine condition.

But...

The net cost? $25,000 to prepare and coat the duct, plus the inconvenience of having the pool out of service for one week. There was also a permanent, aesthetic cost: The gleaming new natatorium now has a white duct, instead of sparkling stainless steel, on a white ceiling

So here’s a lesson for the specifier, owner, or GC: If a building product is classified as “stainless steel” (and, especially, if the price appears to be a bargain), ask the manufacturer exactly what type and grade of stainless steel he or she is selling, and verify that it is suitable for its intended use.

If not, your “stainless” may turn out to be not so stainless.

This article was written by PQA Inspector Dave Lick and is reprinted with permission from the MPI (Master Painters Institute) newsletter. MPI content describes best practices for commercial, institutional, and light industrial painting.

   

Tagged categories: Corrosion; Staining; Stainless steel; Steel; Surface preparation; Surface profile

Comment from Gerald Curtis, (12/20/2013, 10:10 PM)

It is politically incorrect to imply what I infer: Made In China. Nevertheless, there it probably is. Just as the Chinese put lead in the gold crowns that some unwitting dentists bought several years ago as a bargain, so will a society with NO moral Quality Control during production and another society with NO Quality Assurance oversight by distributors, continue to take advantage of those of us who forget that you may get what it is you pay for.


Comment from Salvatore DeLaurentis, (12/22/2013, 8:56 AM)

I have a prefinnished hardwood floor that has water based Basic Emulsion Sealer applied after the prep work it has left streaks and skipped patchy in places. Have difficult getting Finnish off any suggestions ?


Comment from VCBud Jenkins, (1/2/2014, 9:18 PM)

I have used PTS-202 paint remover from Products Techniques to remove paint as a complete film from metal but I don't know if it would work on wood or not. Try a small patch and see.


Comment Join the Conversation:

Sign in to our community to add your comments.

 
 
 

Technology Publishing Co., 1501 Reedsdale Street, Suite 2008, Pittsburgh, PA 15233

TEL 1-412-431-8300  • FAX  1-412-431-5428  •  EMAIL webmaster@durabilityanddesign.com


The Technology Publishing Network

Durability + Design PaintSquare the Journal of Protective Coatings & Linings Paint BidTracker

 

© Copyright 2012-2019, Technology Publishing Co., All rights reserved